16
Before enabling the PID recovery function, make sure the voltage polarity of the
PV modules to ground meets requirement. If there are any questions, contact
the PV module manufacturer or read the corresponding user manual.
PID recovery function and Q at night cannot be enabled at the same time.
If the voltage scheme for the PID protection/recovery function does not meet
the requirement of corresponding PV modules, the PID will not work as ex-
pected or even damage the PV modules.
If the PID recovery function is enabled, it only works at night.
After the PID recovery function is enabled, the voltage of the PV string to
ground is 500Vdc by default, and the default value can be modified through the
App.
AFCI Function(Optional)
AFCI activation
This function can be enabled to detect whether arc occurs in the DC circuit of the inverter.
AFCI self-test
This function is intended to detect whether the AFCI function of the inverter is normal.
2 Product Description User Manual

Table of Contents

Other manuals for Sungrow SG50CX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG50CX and is the answer not in the manual?

Sungrow SG50CX Specifications

General IconGeneral
Max. DC Voltage1100 V
MPPT Voltage Range200 V - 1000 V
Max. Input Current per MPPT26 A
Number of MPPTs4
Rated AC Output Power50 kW
Max. AC Output Current76 A
Frequency50 Hz / 60 Hz
Efficiency98.6%
Start Voltage200 V
Number of DC Inputs per MPPT2
Max. AC Apparent Power55 kVA
AC Voltage Range310 V - 480 V
Power Factor at Rated Power1
Adjustable Power Factor Range0.8 leading - 0.8 lagging
THDi< 3%
DC SwitchYes
AC Surge ProtectionType II
DC Surge ProtectionType II
Protection ClassI
Cooling MethodSmart forced air cooling
Protection DegreeIP66
Protection LevelIP66
Operating Temperature Range-25°C to +60°C
Humidity0-100%
AC Output Voltage3 / N / PE, 220 V / 380 V, 230 V / 400 V