29
WISE User Manual
Operating modes continued
Adjustable room parameters in SuperWISE
Section Description Standard value Min. Max. Unit
Lowest user level
(read/write)
Function
Operating mode Holiday 0 0 1 - Local/Local Set the room in holiday mode.
Operating mode Checked-in 0 0 1 - Local/Installation Set the room in checked in mode.
* Min. airow *** 0 *** l/s Local/Installation Set minimum ow for each mode.
* Temperature setpoint value 22** 0 100 Celsius Local/Local Temperature setpoint value of the current operating case.
*
Temperature oset cooling
mode
1** 0.5 10 Celsius Local/Local
Number of degrees above the set Temperature
setpoint value that is permitted before cooling of the
room occurs.
*
Temperature oset heating
instance
-1** -10 -0.5 Celsius Local/Local
Number of degrees below the set Temperature
setpoint value that is permitted before heating of the
room occurs.
Commissioning Mode water O - Installation/Installation
Select the mode for the required commissioning.
The following modes are available:
Cooling
Heating
Cooling and Heating
Commissioning Mode air O - Installation/Installation
Select the mode for the required commissioning.
The following modes are available:
Unoccupied, min. ow
Occupancy, min ow
Max. ow rate
Holiday, min ow
Percentage of ow area, occupancy
Percentage of maximum ow
Example, when selecting ‘Percentage of maximum
ow’ mode: if the maximum ow is 100l/s and the
user chooses commissioning mode Percentage of
maximum ow to 50% the ow will be 50l/s.
Example, when selecting ‘Percentage of ow range’
mode: if the ow range is 20-100 l/s and the user
chooses commissioning mode Percentage of ow range
to 50% the ow will be 60l/s.
Commissioning Adapted air ow 80 0 100 % Installation/Installation
Setting of the percentage when the you have selected
per cent of the ow range, Occupancy in Mode air.
Commissioning
Max. time commissioning
air
0 0 Hours Installation/Installation
The room returns to normal regulation aer the set time.
0 = No automatic shutdown of commissioning.
Commissioning
Max. time commissioning
water
0 0 Hours Installation/Installation
The room returns to normal regulation aer the set time.
0 = No automatic shutdown of commissioning.
Commissioning Electric mode O - Installation/Installation
Select the mode for the required commissioning. The
following modes are available:
Max. heating
Heating
Maximum heating gives 100% on the output
Heating gives the percentage set on the parameter:
Adapted electrical power.
Commissioning Adapted electrical power 30 0 100 % Installation/Installation
Setting the electrical power during electrical
commissioning
Commissioning
Maximum time for
electrical commissioning
0 0 5000 Hours Installation/Installation
Specify the maximum time for electrical
commissioning
*Set separately for the modes Occupancy, Unoccupied, Holiday, Summer night cooling and Morning heating.
**Standard value applies for Occupancy.
***Depending on the set min/max ow on the room products.