Swegon reserves the right to alter specications. 20220323
68
WISE User Manual
Periodic valve operation
Why periodic valve operation?
In order to ensure that valves do not jam when they are not used
for long periods, for example, heating valves during the summer,
they are regularly operated.
How does periodic valve operation
work?
Periodic valve operation occurs automatically and does not need
to be activated manually by the user. Periodic valve operation
occurs on all outputs that are congured to control water valves.
The sequence is as follows: 0% on outputs for cooling for 3
minutes, then 100% for 3 minutes. The same sequence is then
performed on the heating output.
Periodic valve operation starts automatically for the rst time
in unoccupancy mode every Friday aer 00:01, if the room is in
occupancy mode, periodic valve operation is carried out regard-
less of occupancy or unoccupancy on Monday at 00:01.
LED operating status
How does LED operating status work?
The product’s LED normally shows its operating status. There
is a setting to switch o the LED for normal operations if it is
perceived as disturbing.