WISE User Manual
Additional moisture
Why additional moisture group?
In an additional moisture group, several rooms can share addi-
tional moisture values or regulate with the help of each other’s
values. It is also possible to compare the measured additional
moisture of products and to regulate on an average value of
several rooms or the highest/lowest calculated value.
Adjustable group parameters in SuperWISE
Section Description Standard value Min. Max. Unit
Lowest user level
(read/write)
Function
Function
Additional moisture
operating mode
Average value - - - Local/Installation
What value to use in the group
Average value
Lowest
Highest
Change over
Why a change-over group?
A Change-over group can be used so rooms in the group can be
controlled with either hot or cold water in the pipes. A Change-
over system can then be used if you want to be able to cool and
heat using the same pipes.
How does a change-over group work?
A Change-over group works by measuring the supply ow
temperature of the water at one point and then sending this to
the group. The supply ow temperature can also be acquired via
BMS or from a congured value in SuperWISE.
It is also possible to choose whether cooling or heating is available,
either in SuperWISE or via BMS.
- Heating: Sets the groups Change-over temperature to °C.
- Cooling: Sets the groups Change-over temperature to °C
A choice such as this overrides the measured Change-over
temperature.
There are three dierent operating modes for each Change-over
group:
. Heating: The Change-over-group temperature is set to °C.
. Cooling: The Change-over-group temperature is set to °C.
. Measured temperature: The Change-over temperature will
then be the measured supply ow temperature.
When there is no Change-over temperature in a Change-over
group, the external Change-over temperature in the room will
be used. This can be specied in SuperWISE, or communicated
via BMS.