WISE User Manual
Constant ow regulation
Why constant ow regulation?
Constant ow regulation is used when a constant ow is to be
maintained in a duct.
How to establish constant ow?
The ow is measured at the damper where the ow is increased
or decreased by closing or opening the damper. Constant ow
regulation can occur on the supply air (FS*) and extract air
damper (FE*).
Constant ow regulation is congured in IC Design, depending
on whether it is a supply air damper (FS) or extract air damper
(FE). Supply/extract air dampers (FS/FE) are congured by
setting a setpoint value for the air ow.
Adjustable product parameters in SuperWISE
Section Description Standard value Min. Max. Unit
Lowest user level
(read/write)
Function
Air ow Constant air ow function 0 0 1 - Local/Installation
Constant ow enabled or disabled on ow
controlled products.
Air ow Constant air ow 0 l/s Local/Installation
Flow setpoint value for constant ow
damper.
* PS = Pressure Supply, PE = Pressure Extract, PED = Pressure Extract Diverted,
FS = Flow Supply, FE = Flow Extract, OS = Optimize Supply, OE = Optimize Extract
WISE Damper
( FS)
WISE Damper
( FE)
ZON
Basic circuit diagram, Constant pressure regulation