WISE User Manual
Air quality
Why air quality groups?
In an air quality group it is possible for several rooms to share air
quality sensors or regulate with the help of each other’s sensors.
It is also possible to compare the measured air quality of prod-
ucts and to regulate on an average value of several sensors’ air
quality or the highest/lowest measured air quality.
The air quality in the WISE system can be measured and
regulated either by VOC or CO
2
or RH.
Adjustable group parameters in SuperWISE
Section Description Standard value Min. Max. Unit
Lowest user level
(read/write)
Function
Function Air quality mode VOC Average value - Local/Installation
What value to use in the group
Average value
Lowest
Highest
Function Mode air quality CO
2
Average value - Local/Installation
What value to use in the group
Average value
Lowest
Highest
Function Air quality RH mode Average value - Local/Installation
What value to use in the group
Average value
Lowest
Highest
Function Status, room
Contribute and
follow
- Local/Installation
States whether a room should use a function group value or only
contribute to the function group value without using it.
Contribute and follow
Contribute only
Follow only
Temperature
Why temperature groups?
In a temperature group it is possible for several rooms to share
temperature sensors or regulate with the help of each other’s
sensors. It is also possible to compare the measured temperatures
of products and to regulate on an average value of several sensors’
temperatures or the highest/lowest measured temperature.
There are a number of dierent temperature sensors, with varying
application areas, to use:
• WISE SMB
• WISE RTS
• WISE RTA
• WISE IAQ
• WISE IRT
• WISE OCS
• WISE RTS
See the WISE System guide or separate product documentation
for further information.
Adjustable group parameters in SuperWISE
Section Description
Standard
value
Min. Max. Unit
Lowest user level
(read/write)
Function
Function Mode temperature Average value - Local/Installation
What value to use in the group.
Average value
Lowest
Highest
Function Status, room
Contribute and
follow
- Local/Installation
States whether a room should use a function group value or only
contribute to the function group value without using it.
Contribute and follow
Contribute only
Follow only