20220323 Swegon reserves the right to alter specications.
63
WISE User Manual
Outdoor temperature via communication
(GOLD)
The aim of this function is to use one or more outdoor temper-
ature sensors for several air handling units. All GOLD units with
the function activated are included in this function. An average
outdoor temperature is calculated from all existing outdoor
temperature sensors, this temperature is then written to GOLD.
Adjustable unit parameters in SuperWISE
Section Description Standard value Min. Max. Unit
Lowest user level
(read/write)
Function
Air handling unit
Air handling unit,
authorisation mode
Read and write None Read - Installation/Installation Rights for write/read.
Air optimization functions
Why optimize the air handling unit?
The main purpose of the air optimization functions is to reduce
energy consumption, but the functions also reduce the risks of
experiencing problems with disturbing noise from the ventilation
system.
There are dierent types of optimization:
• Duct pressure optimization
• Supply air temperature optimization
How does pressure optimization of
the supply air temperature work?
Optimization reduces/increases the fan speed by analysing the
damper positions on the products that lie directly under the air
handling unit. There is a congurable ag on each product that
indicates whether the product should be included or excluded
from the optimization.
GOLD
SuperWISE has support for communication with the GOLD and
COMPACT air handling unit. For other air handling units (referred to
as “Generic air handling unit” in the SuperWISE interface), a BMS
system is required to read and write the optimization parameters.
The parameters can be found on the “Documentation” tab in the
SuperWISE interface where it’s possible to create a list.
Optimization in SuperWISE
Optimization settings for the system’s air handling unit.
Settings to optimize the system’s air handling unit. Select the air
handling unit to be optimized.
The function is activated with a slider at the top of the page,
which establishes direct contact between the relevant air
handling unit and SuperWISE. GOLD version E/F as well as
Compact Unit, Top and LP communicate with SuperWISE, other
air handling units via Modbus/BACnet.
The Reading section shows the air handling unit’s current
operating information while settings for optimization are found
under Optimization.
Any settings are executed by clicking on Save, or Undo to return
to the existing settings (1). Implemented changes are saved in
the Change log.
1