RETRIEVE ALARMS (Contd)
condtype: FA = fuse alarm
SYNCCLK = output port failed
HLDOVRSYNC = clock in the holdover mode
SYNC = input reference failed
FRNGSYNC = clock in the freerunning mode
SLTMSIG = input references unlocked
INT = card failed
FSTSYNC = clock in the fast-converge mode
BPV = bipolar violations
CRC = cyclic redundancy check errors
OOF = out of frame errors
LOS = loss of signal
AIS = alarm indication signal
<null> = all of the above condtypes
Note: If the aid is MRC-1 or MRC-2, the condtypes AIS, BPV, CRC, OOF, and LOS are
to be used only if E1 is selected as the input; if analog is the input, and AIS, BPV, CRC,
OOF, or LOS are the condition types, the command will be denied.
condtype: For PSM only:
MTIE1 = maximum time interval error at 1 second
MTIE4 = maximum time interval error at 4 seconds
MTIE16 = maximum time interval error at 16 seconds
MTIE64 = maximum time interval error at 64 seconds
MTIE128 = maximum time interval error at 128 seconds
MTIE512 = maximum time interval error at 512 seconds
MTIE900 = maximum time interval error at 900 seconds
TVAR1 = time variance error at 1 second
TVAR4 = time variance error at 4 seconds
TVAR16 = time variance error at 16 seconds
TVAR64 = time variance error at 64 seconds
TVAR128 = time variance error at 128 seconds
<null> = all condtypes, except those listed for GTI
condtype: For GTI only:
FA = fuse A
FB = fuse B
GPSLOS = GPS loss of signal
GPSINVLD = GPS timing is invalid
GTINOINPUTS = no oscillator A or B and no GPS
GTIOUTFLT = output of the GTI has been faulted
GTIFAILx = hard failure, where x = 1 through 5 (the numbers 1-5 are
diagnostic codes for field service/engineering use only)
OSCALOS = no OSC A input
OSCBLOS = no OSC B input
OSCATOL = OSC A out of tolerance
OSCBTOL = OSC B out of tolerance
GTRPWR = power supply has been faulted by a short, an open, or
equipment failure
GTRFREQTOL = 4 kHz output from the GTR is not phase-locked
GTRSAT = insufficient satellites

Table of Contents

Other manuals for Symmetricom TimeProvider 500 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom TimeProvider 500 series and is the answer not in the manual?

Symmetricom TimeProvider 500 series Specifications

General IconGeneral
BrandSymmetricom
ModelTimeProvider 500 series
CategoryData Loggers
LanguageEnglish

Related product manuals