106
*TST?
Query Self-test query. If one or more tests fail, "1" is returned. Error is stored in the
*WAI
Function Configures the instrument to wait for all pending operations to complete before
executing any additional commands over the interface.
ABORt
Function This command cancels any sequencer actions in progress. It returns the trigger
system to the Idle state.
TWI bit is cleared in the Status Register Group Condition Register.
5.14
SCPI Subsystem Commands
Subsystem commands are specific to Power Supply functions. Those can be a single command or
a group of commands. Groups are comprised of commands that extend one or more levels below
the root.
Commands followed by a question mark (?) take only the query form.
5.14.1 Display Subsystem
DISPlay[:WINDow]:STATe <Bool>
Function Sets front panel (Display, Buttons) OFF/ON.
Power switch is active, disregarding command OFF/ON state.
NOTE:
Display & Buttons are active after AC recycle or after Power Switch OFF (above four seconds at
Power Switch OFF state).
DISPlay[:WINDow]:FLASh <Bool>
DISPlay[:WINDow]:TEST <Bool>
Turns all display segments & LEDs on.