EasyManua.ls Logo

TDK-Lambda GENESYS GEN 2400W Series - Fuse Rating

TDK-Lambda GENESYS GEN 2400W Series
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
83-517-000 Rev. A
77
Table 9-1: Troubleshooting Guide (continued)
SYMPTOM
CHECK
ACTION
REF
Output Voltage will not
adjust. Front panel CV LED
is illuminated.
Check if output voltage is
adjusted above OVP
setting or below UVL
setting.
Set OVP or UVL so their
settings will not limit the
Output voltage.
5.3
5.4
Output Current will not
adjust. Front panel CV LED
is illuminated.
Is the unit in Constant-
Voltage (CV) mode ?
Check Output current limit
and Output voltage setting
5.2
Large voltage ripple present
across Output.
Is the power supply in
remote sense ?
Is the voltage drop on the
load wire too high ?
Check load and sense
wires connection for noise
and impedance effects.
Minimize the voltage drop
on the load wires.
3.9.4
3.9.8
No output. Display indicates
OUP
Over-Voltage Protection
(OVP) circuit is tripped.
Turn OFF the AC Input
power switch. Check load
connections. If J1 Analog
Programming is used,
check if the OVP is set
lower than the output.
5.3
No output. Front panel
ALARM LED is blinking.
Display indicates “EnA
Check rear panel J1
ENABLE connection.
5.8
SW1 DIP-switch setting.
4.4
Display indicates “SO
Check rear panel J1
Output Shut-Off (SO)
connection.
5.7
Display indicates “OTP
Check if air intake or
exhaust are blocked.
Check if the unit is
installed adjacent to heat
generating equipment.
5.12
Display indicates “Fb
Check Foldback setting
and load current.
5.5
Poor Load regulation.
Front panel CV LED is
illuminated.
Are sensing wires
connected properly ?
Connect the sense wires
according to User’s
Manual instructions.
3.9.8
The front panel controls are
non-functional.
Is the power supply in
Local-Lockout mode ?
Turn Off the AC Input
power and wait until the
display turns OFF. Turn
on the AC Input power
and press the front panel
REM/LOC button.
7.2.5
9.7 FUSE RATING
There are no user-replaceable fuses in the power supply. Internal fuses are sized for fault protection and if a
fuse opened, it would indicate that service is required. Fuse replacement should be made by qualified technical
personnel. Refer to Table 9-2 for a listing of the internal fuses.
Fuse designation
Single-Phase, 190-240VAC
Three-Phase, 190-240VAC
INPUT FUSE
F301, F302:
30A, 250VAC, Fast Acting
F321, F322, F323:
15A, 250VAC, Fast-Acting
Table 9-2 Internal Fuses

Table of Contents

Related product manuals