83-517-000 Rev. A
65
NOTES:
1. In Advanced Parallel” mode (refer to Section 5.15.2), “n” is the total system Output current.
2. In Advanced Parallel mode, MC? returns the Master unit Output current multiplied by the Number of
Slave units + 1.
Global Output Commands 7.7.6
7.7.6.1 General
All power supplies, even if not the currently addressed power supply, receiving a Global command will execute
that Global command. No response (to the controller/PC issuing the command) will be returned to the
controller/PC. The controller/PC issuing the Global command will be responsible to delay any other
communications until the command is executed. The suggested delay is 200 milliseconds minimum.
If the Global command contains an error, out of range values for example, no error report will be sent to the
issuing controller/PC.
#
Command
Description
1
GRST
Global Reset. Brings the power supply to a safe and known state:
Output voltage: 0V, Output current: 0A, OUT: Off, Local/Remote: Remote, AST:
OFF, OVP: Maximum, UVL: 0V.
The conditional register (FLT and STAT) are updated. Other registers are not
changed.
Non-latching faults (FB, OVP, SO) are cleared, OUT fault stays
2
GPV n
Sets the Output voltage value in Volts. The range of Output voltage values is shown in
Table 7-3. ‘n’ may be up to 12 characters plus decimal point
3
GPC n
Program the Output current value in Amperes. The range of Output current values is
shown in Table 7-4. ‘n’ may be up to 12 characters plus decimal point
4
GOUT
Turns the output to ON or OFF:
OUT 1 (or OUT ON)” = Turn Output ON
OUT 0 (or OUT OFF)” = Turn Output OFF; clears CV and CC bits in the Status
Condition (STAT) register.
OUT ON will respond with “E07 if the output cannot be turned ON because of a
latching fault (OTP, AC, ENA, SO) shutdown.
5
GSAV
Saves “Present Settings. Same settings as power-down last settings listed in Section
5.13 except the unit Address and Baud rate are not saved to EPROM memory. These
settings are erased when the power supply AC Input power is switched OFF and the
new ‘Last Settings are saved.
6
GRCL
Recalls “Last Settings. Settings are from last AC Input power-down or from last SAV
or GSAV command. Unit Address and Baud rate are not recalled so serial
communication is not interrupted.
Model
VOrated
Minimum
(V)
Maximum
(V)
Model
IOrated
Minimum
(A)
Maximum
(A)
8
0.0000
8.000
300
000.00
300.00
10
00.000
10.000
240
000.00
240.00
16
00.000
16.000
150
000.00
150.00
20
00.000
20.000
120
000.00
120.00
30
00.000
30.000
80
00.000
80.000
40
00.000
40.000
60
00.000
60.000
60
00.000
60.000
40
00.000
40.000
80
00.000
80.000
30
00.000
30.000
100
000.00
100.00
24
00.000
24.000
150
000.00
150.00
16
00.000
16.000
300
000.00
300.00
8
0.0000
8.0000
600
000.00
600.00
4
0.0000
4.0000
Table 7-3: Voltage programming range Table 7-4: Current programming range