EasyManua.ls Logo

TESTO 340 - Oil Flow Rate Measurement; Flow Speed (m;s) Measurement

TESTO 340
65 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
G.2.6 Oil flow rate
The Oil flow rate function is only available if the activated fuel is an oil.
Calling up the function:
Measurements Oil flow rate .
Measuring:
1
Enter the flow rate:
Flowrate Enter the value .
2
Enter the oil pressure:
Oil pressure Enter the value .
- The calculated oil burner output is displayed.
3
Copy the values to the
Flue gas menu: OK Copy readings .
- The
Measurements menu is opened.
G.2.7 m/s
A Pitot tube must be connected, the connection cable for the Pitot tube thermo-
couple must be connected to the instrument probe socket.
To measure flow speed, air flow and mass flow the parameters of cross-section shape,
cross-section surface area, Pitot factor and offset factor must be set, see
Location
,p.
23.
Do not measure for longer than 5 min, as the drift of the pressure sensor means that
the readings could be outside the tolerance limits.
Calling up the function:
Measurements m/s .
Measuring:
1
Start measuring: .
- Pressure zeroing (5 s).
2
Position the Pitot tube in the duct. The display showing the measured flow speed
(Speed) helps when positioning the probe.
- The reading is displayed.
3
Stop measuring: .
- The reading is recorded.
Option:
To print the reading: .
4
Accept the reading: .
- The
Measurements menu is opened.
OK
Print
Stop
Start
OKOK
OK
OKChange
OKChange
OKOK
G. Measuring