MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20 Page 99 THOMSON TECHNOLOGY
4470 VDO water temp. input 3.2
No. Setting Min. setting Max. setting Factory
setting
4471 VDO 3.2 Set point 0°C 150°C 95°C
4472 VDO 3.2 Delay 0.0 s 100.0 s 5.0 s
4473 VDO 3.2 Output A R0 (none) R26 (relay 26) R0 (none)
4474 VDO 3.2 Output B R0 (none) R26 (relay 26) R0 (none)
4475 VDO 3.2 Enable OFF ON OFF
4476 VDO 3.2 Fail class See description of fail classes
4630 VDO low coolant temp. input 3.3
No. Setting Min. setting Max. setting Factory
setting
4631 VDO 3.3 Set point -50°C 50°C 10°C
4632 VDO 3.3 Delay 0.0 s 10.0 s 1.0 s
4633 VDO 3.3 Output A R0 (none) R26 (relay 26) R0 (none)
4634 VDO 3.3 Output B R0 (none) R26 (relay 26) R0 (none)
4635 VDO 3.3 Enable OFF ON OFF
4636 VDO 3.3 Fail class See description of fail classes
VDO type: See functional description.