MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20 Page 46 THOMSON TECHNOLOGY
Fail class
All the activated alarms of the MEC 310 must be configured with a fail class. The fail classes define
the category of the alarms and the subsequent action of the alarm.
Four different fail classes are available:
Action
Fail class
Alarm
horn
relay*
Alarm
display
Block
engine
start
Open gen.
breaker
Stop
generator
Cooldown Shutdown
0 Warning X X
1 Trip of GB X X X
2 Trip and stop
X X x X X X
3 Shutdown X X x X X X
* When alarm horn relay output is selected active.
Fail class configuration
The fail class can be selected for each alarm function via the TPS 300 software. To change the fail
class via the TPS 300 software, the alarm function to be configured must be selected. Select the
desired fail class in the fail class roll down panel.
The fail class roll down panel is activated, and the individual functions are ready for selection.