EasyManuals Logo

THOMSON MEC 310#GENSET CONTROLLER User Manual

THOMSON MEC 310#GENSET CONTROLLER
119 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20 Page 47 THOMSON TECHNOLOGY
Service timers
The controller can monitor two different maintenance intervals:
Service timer 1
Service timer 2
The service timers both have the possibility of a setting for days (total elapsed time) and hours
(running hours). The day setting counts whenever there is aux. supply on the MEC 310, and the
hours count when a running feedback is present. It is possible to set the service timers to count up
or count down.
The service timer alarm activates whenever the amount of days or the amount of running hours has
expired. If the service timer is set to count down the display will shown 0 days or 0 hours; if the
service timer is set to count up the display will show the amount of days or hours programmed in
the parameter.
When the service timer alarm appears it can be acknowledged but the alarm will not become
inactive before the service timer has been reset. This can be done from the display or via the TPS
300 software. Whenever the service timer is reset, the timer will start counting from the initial value.
The service timer alarm must be reset in the parameter list of the MEC 310 or via
the TPS 300 software in parameter 6116 or 6126 to remove the actual alarm.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the THOMSON MEC 310#GENSET CONTROLLER and is the answer not in the manual?

THOMSON MEC 310#GENSET CONTROLLER Specifications

General IconGeneral
BrandTHOMSON
ModelMEC 310#GENSET CONTROLLER
CategoryController
LanguageEnglish

Related product manuals