MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20 Page 102 THOMSON TECHNOLOGY
4960 Battery low 1
No. Setting Min. setting Max. setting Factory
setting
4961 Battery low V
*
Set point 6.0V 28.0V 16.0V
4962 Battery low V
*
Timer 0.0 s 999.0 s 1.0 s
4963 Battery low V Relay output A R0 (none) R26 (relay 26) R0 (none)
4964 Battery low V Relay output B R0 (none) R26 (relay 26) R0 (none)
4965 Battery low V Enable OFF ON ON
4970 Battery high voltage
No. Setting Min. setting Max. setting Factory
setting
4971 Battery high V
*
Set point 15.0V 40.0V 28.0V
4972 Battery high V
*
Timer 0.0 s 10.0 s 1.0 s
4973 Battery high V Relay output A R0 (none) R26 (relay 26) R0 (none)
4974 Battery high V Relay output B R0 (none) R26 (relay 26) R0 (none)
4975 Battery high V Enable OFF ON OFF
5000...5060 Relay functions
No. Setting First/min.
setting
Second/max.
setting
Factory
setting
50X1 Relay X Function Alarm Limit Alarm
50X2 Relay X Off delay 0.0 s 999.9 s 5.0 s
If option A is present, then parameter 5050 and 5060 are not available.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the THOMSON MEC 310#GENSET CONTROLLER and is the answer not in the manual?

THOMSON MEC 310#GENSET CONTROLLER Specifications

General IconGeneral
BrandTHOMSON
ModelMEC 310#GENSET CONTROLLER
CategoryController
LanguageEnglish

Related product manuals