MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20 Page 110 THOMSON TECHNOLOGY
6940 Alarm LED function
No. Setting Min. setting Max. setting Factory
setting
6941 Alarm LED function Customer Red/Red
(Warning/
Shutdown)
Amber/Red
(Warning/
Shutdown)
Red/Red
(Warning/
Shutdown)
7560 Engine I/F
7570 EIC comm. error
No. Setting Min. setting Max. setting Factory
setting
7571 EI comm. error Delay 0.0 s 100.0 s 0.0 s
7572 EI comm. error Relay output A Not used Not used
7573 EI comm. error Relay output B Not used
Option
dependent
Not used
7574 EI comm. error Enable OFF ON OFF
7575 EI comm. error Fail class Unit dependent Warning
No. Setting Min. setting Max. setting Factory setting
7561 Engine I/F Engine type
OFF
DDEC
EMR
JDEC
Iveco
Perkins
Caterpillar
Volvo Penta EMS
Volvo Penta EMS 2
Scania EMS
Scania EMS S6
MDEC 2000/4000 M.302
MDEC 2000/4000 M.303
MTU ADEC
Cummins CM850
Generic J1939
OFF
7562 Engine I/F Node CANopen ID
1 128 6
7563 Engine I/F EIC Controls
on off on
7564 Engine I/F EIC Auto View
on off on
Please choose MDEC 2000/4000 M.303, when M.201 or M.304 is required.
Menu 7562 is only used when MTU ADEC is selected as engine type.