MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20 Page 111 THOMSON TECHNOLOGY
7580 EIC warning
No. Setting Min. setting Max. setting Factory
setting
7581 EIC warning Delay 0.0 s 100.0 s 0.0 s
7582 EIC warning Relay output A Not used Not used
7583 EIC warning Relay output B Not used
Option
dependent
Not used
7584 EIC warning Enable OFF ON OFF
7585 EIC warning Fail class Unit dependent Warning
7590 EIC shutdown
No. Setting Min. setting Max. setting Factory
setting
7591 EIC shutdown Delay 0.0 s 100.0 s 0.0 s
7592 EIC shutdown Relay output A Not used Not used
7593 EIC shutdown Relay output B Not used
Option
dependent
Not used
7594 EIC shutdown Enable OFF ON OFF
7595 EIC shutdown Fail class Unit dependent Shutdown
7600 EIC overspeed
No. Setting Min. setting Max. setting Factory
setting
7601
EIC overspeed
Set point 0 % 400 % 107 %
7602 EIC overspeed Delay 0.0 s 100.0 s 2.0 s
7603 EIC overspeed Relay output A Not used Not used
7604 EIC overspeed Relay output B Not used
Option
dependent
Not used
7605 EIC overspeed Enable OFF ON OFF
7606 EIC overspeed Fail class Unit dependent Warning
7610 EIC coolant t. 1
No. Setting Min. setting Max. setting Factory
setting
7611
EIC coolant t. 1 Set point -40 deg. 210 deg. 100 deg.
7612 EIC coolant t. 1 Delay 0.0 s 100.0 s 5.0 s
7613 EIC coolant t. 1 Relay output A Not used Not used
7614 EIC coolant t. 1 Relay output B Not used
Option
dependent
Not used
7615 EIC coolant t. 1 Enable OFF ON OFF
7616 EIC coolant t. 1 Fail class Unit dependent Warning
7620 EIC coolant t. 2
No. Setting Min. setting Max. setting Factory
setting
7621
EIC coolant t. 2 Set point -40 deg. 210 deg. 110 deg.
7622 EIC coolant t. 2 Delay 0.0 s 100.0 s 5.0 s
7623 EIC coolant t. 2 Relay output A Not used Not used
7624 EIC coolant t. 2 Relay output B Not used
Option
dependent
Not used
7625 EIC coolant t. 2 Enable OFF ON OFF
7626 EIC coolant t. 2 Fail class Unit dependent Warning