MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20 Page 112 THOMSON TECHNOLOGY
7630 EIC oil press. 1
No. Setting Min. setting Max. setting Factory
setting
No. Setting Min. setting Max. setting Factory
setting
7631
EIC oil press. 1 Set point 0.0 bar 10.0 bar 2.0 bar
7632 EIC oil press. 1 Delay 0.0 s 100.0 s 5.0 s
7633 EIC oil press. 1 Relay output A Not used Not used
7634 EIC oil press. 1 Relay output B Not used
Option
dependent
Not used
7635 EIC oil press. 1 Enable OFF ON OFF
7636 EIC oil press. 1 Fail class Unit dependent Warning
7640 EIC oil press. 2
No. Setting Min. setting Max. setting Factory
setting
7641
EIC oil press. 2 Set point 0.0 bar 10.0 bar 1.0 bar
7642 EIC oil press. 2 Delay 0.0 s 100.0 s 5.0 s
7643 EIC oil press. 2 Relay output A Not used Not used
7644 EIC oil press. 2 Relay output B Not used
Option
dependent
Not used
7645 EIC oil press. 2 Enable OFF ON OFF
7646 EIC oil press. 2 Fail class Unit dependent Warning
7650 EIC oil Temp. 1
No. Setting Min. setting Max. setting Factory
setting
7651
EIC oil temp. 1 Set point 0 C 300 C 40 C
7652 EIC oil temp. 1 Delay 0.0 s 100.0 s 5.0 s
7653 EIC oil temp. 1 Relay output A Not used Not used
7654 EIC oil temp. 1 Relay output B Not used
Option
dependent
Not used
7655 EIC oil temp. 1 Enable OFF ON OFF
7656 EIC oil temp. 1 Fail class Unit dependent Warning
7660 EIC oil Temp. 2
No. Setting Min. setting Max. setting Factory
setting
7661
EIC oil temp. 2 Set point 0 C 300 C 40 C
7662 EIC oil temp. 2 Delay 0.0 s 100.0 s 5.0 s
7663 EIC oil temp. 2 Relay output A Not used Not used
7664 EIC oil temp. 2 Relay output B Not used
Option
dependent
Not used
7665 EIC oil temp. 2 Enable OFF ON OFF
7666 EIC oil temp. 2 Fail class Unit dependent Warning
9110 Password
No. Setting Min. setting Max. setting Factory
setting
9116 Password Customer 0 9999 2000
9117 Password Service 0 9999 2001
User password
If you forget the password, contact Thomson Technology for details.