EasyManua.ls Logo

THOMSON MEC 310#GENSET CONTROLLER - Page 116

THOMSON MEC 310#GENSET CONTROLLER
119 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20 Page 112 THOMSON TECHNOLOGY
7630 EIC oil press. 1
No. Setting Min. setting Max. setting Factory
setting
No. Setting Min. setting Max. setting Factory
setting
7631
EIC oil press. 1 Set point 0.0 bar 10.0 bar 2.0 bar
7632 EIC oil press. 1 Delay 0.0 s 100.0 s 5.0 s
7633 EIC oil press. 1 Relay output A Not used Not used
7634 EIC oil press. 1 Relay output B Not used
Option
dependent
Not used
7635 EIC oil press. 1 Enable OFF ON OFF
7636 EIC oil press. 1 Fail class Unit dependent Warning
7640 EIC oil press. 2
No. Setting Min. setting Max. setting Factory
setting
7641
EIC oil press. 2 Set point 0.0 bar 10.0 bar 1.0 bar
7642 EIC oil press. 2 Delay 0.0 s 100.0 s 5.0 s
7643 EIC oil press. 2 Relay output A Not used Not used
7644 EIC oil press. 2 Relay output B Not used
Option
dependent
Not used
7645 EIC oil press. 2 Enable OFF ON OFF
7646 EIC oil press. 2 Fail class Unit dependent Warning
7650 EIC oil Temp. 1
No. Setting Min. setting Max. setting Factory
setting
7651
EIC oil temp. 1 Set point 0 C 300 C 40 C
7652 EIC oil temp. 1 Delay 0.0 s 100.0 s 5.0 s
7653 EIC oil temp. 1 Relay output A Not used Not used
7654 EIC oil temp. 1 Relay output B Not used
Option
dependent
Not used
7655 EIC oil temp. 1 Enable OFF ON OFF
7656 EIC oil temp. 1 Fail class Unit dependent Warning
7660 EIC oil Temp. 2
No. Setting Min. setting Max. setting Factory
setting
7661
EIC oil temp. 2 Set point 0 C 300 C 40 C
7662 EIC oil temp. 2 Delay 0.0 s 100.0 s 5.0 s
7663 EIC oil temp. 2 Relay output A Not used Not used
7664 EIC oil temp. 2 Relay output B Not used
Option
dependent
Not used
7665 EIC oil temp. 2 Enable OFF ON OFF
7666 EIC oil temp. 2 Fail class Unit dependent Warning
9110 Password
No. Setting Min. setting Max. setting Factory
setting
9116 Password Customer 0 9999 2000
9117 Password Service 0 9999 2001
User password
If you forget the password, contact Thomson Technology for details.