MEC 310 GENSET CONTROLLER
PM075 REV 2 09/08/20 Page 87 THOMSON TECHNOLOGY
Each parameter description is structured according to the same principles. Under the parameter title
heading, the detailed parameter descriptions are illustrated and presented. First, a table indicating the
parameter facts related to the individual parameter title is presented:
4310 VDO input – oil pressure 2.x
No. Setting Min. setting Max. setting Factory
setting
4311 Oil pressure 2.1 Set point 0.0 bar 10.0 bar 4.0 bar
4312 Oil pressure 2.1 Delay 0.0 s 100.0 s 5.0 s
4313 Oil pressure 2.1 Output A R0 (none) R26 (relay 26) R0 (none)
4314 Oil pressure 2.1 Output B R0 (none) R26 (relay 26) R0 (none)
4315 Oil pressure 2.1 Enable OFF ON OFF
4316 Oil pressure 2.1 Fail class Warning Shutdown Trip of GB
The first column indicates the channel number in the TPS 300.
The second column indicates the changeable setting in the TPS 300 software.
The third and fourth columns indicate the minimum/maximum set point available for this setting.
The fifth column indicates the default set point of the unit from the factory.
When it is necessary, additional information will be supplied after the table in order to make the
individual parameter descriptions as informative as possible.