NVA100X-D - Manual - 02 - 2016
SETTING AND COMMISSIONING
SET
NVA100X-D_menuset1.ai
PROCEED SET MENU’
BASE >>
PROCEED PROFILE A MENU’
Plant
..................
Reading RELATIVE
Un 100 V
Unp 20000 V
UEn 100 V
UEnp 20000 V
InH 5 A
InpH 100 A
InHL 5 A
InpL 100 A
IEn1 1 A
IEn1p 1000 A
IEn2 1 A
IEn2p 1000 A
Ing 100 A
Inref 0 A
NumSides 2
RefSide H
MatchType INTERNAL
Magnitude matching
factor M(H)
Magnitude matching
factor M(L)
64REF Wrong nominal
settings ME(H)
fn 50 Hz
LANGUAGE English
INPUT SEQUENCE >>
I-Sequence
IL1-IL2-IL3 Def.
V-Sequence
UL1-UL2-UL3 Def.
SELF-TEST RELAY >>
Minor failure
alarm NO
Self-test relay -
START CONTROL >>
CLP Source IRUN
IRUN 0.10 IB
MR Enable OFF
PROFILE A
>>
PROFILE
SELECTION >>
Active Profile A
MMI >>
Param. setting
enable ON
Modules data
visualization
ASSIGNED MODULES
POLARITY >>
A1-A2 NORMAL
A3-A4 NORMAL
A5-A6 NORMAL
A7-A8 NORMAL
B3-B4 NORMAL
B5-B6 NORMAL
B7-B8 NORMAL
B9-B10 NORMAL
C1-C2 NORMAL
C3-C4 NORMAL
C5-C6 NORMAL
C7-AC NORMAL
TRANSFORMER >>
Snt 6.93 MVA
VntH 8.0 kW
IntH 0 A
mH 0.00
GndH Out
ConnH D
VectorGroup 0
VntL 8.0 kW
IntL 0 A
mL 0.00
GndL Out
ConnH y
VectorGroup 0
Logic Active-ON
ON Delay
IN1-1 tON 0 s
OFF Delay
IN1-1 tOFF 0 s
IN1-1 matching None
Logic Active-ON
ON Delay
IN1-x tON 0 s
OFF Delay
IN1-x tOFF 0 s
IN1-2 matching None
Logic Active-ON
ON Delay
IN1-2 tON 0 s
OFF Delay
IN1-2 tOFF 0 s
IN1-2 matching None
INPUTS
IN1-1...IN1-16 >>
Binary input IN1-1
Setpoints >>
Binary input IN1-2
Setpoints >>
Binary input IN1-x
Setpoints >>
IB >>
IB 1.00 In
U< Enable OFF
Type Characteristic
U<Curve
DEFINITE
U<def OFF
0.5 Un
tU<def 1 s
U<inv OFF
0.5 Un
tU<inv 10 s
U<BF OFF
Relays U<
U<ST-K -
U<TR-K -
LEDs U<
U<ST-L -
U<TR-L -
Utype27 Uph-ph
Rof>SYNC 0 Hz
U<<def OFF
0.5 Un
tU<<def 1 s
U<<BLK1 OFF
U<disbyU<< OFF
U<<BF OFF
Relays U<<
U<<ST-K -
U<<TR-K -
LEDs U<<
U<<ST-L -
U<<TR-L -
27 >>
Common >>
U< Element >>
U<< Element >>
Logic ENERGIZED
OPERATION MODE
LATCHED
Minimum pulse width
KC1-1 tTR 150 ms
Logic ENERGIZED
OPERATION MODE
LATCHED
Minimum pulse width
KC1-2 tTR 150 ms
Logic ENERGIZED
OPERATION MODE
LATCHED
Minimum pulse width
KCx-x tTR 150 ms
RELAYS
KC1-1...KC1-8 >>
KC1-1 relay
Setpoints >>
KC1-2 relay
Setpoints >>
........
KCx-x relay
Setpoints >>
LEDS
ON MMI >>
Start LED logic
NO LATCHED
Trip LED logic
NO LATCHED
LED 1 logic
NO LATCHED
LED 2 logic
NO LATCHED
LED 3 logic
NO LATCHED
LED 4 logic
NO LATCHED
LED 5 logic
NO LATCHED
LEDS
LED1-1...LED1-8 >>
LED1-1 logic
NO LATCHED
LED1-2 logic
NO LATCHED
LED1-3 logic
NO LATCHED
LED1-4 logic
NO LATCHED
LED1-x logic
NO LATCHED
LED1-8 logic
NO LATCHED
U1<def enable OFF
0.5 En
tU1<def 1 s
U1<BLK1 OFF
U1<BF OFF
Relays U1<
U1<ST-K -
U1<TR-K -
LEDs U1<
U1<ST-L -
U1<TR-L -
27V1 >>
U1< Element >>
21 >>
Z<< Element >>
Z< Element >>
tZ<RES 0.10 s
Z<def OFF
1.00 Zn
tZ<def 1.00 s
Z<BLK1 OFF
Z<BLK2IN OFF
Z<BLK2OUT OFF
Z<BF OFF
Relays Z<
Z<ST-K -
Z<TR-K -
LEDs Z<
Z<ST-L -
Z<TR-L -
(U/f)AL Enable OFF
t(U/f)>RES 0.10 s
(U/f)ALdef enable OFF
(U/f)ALdef 1.00 Un/fn
t(U/f)ALdef 1.00 s
(U/f)ALBLK1 OFF
(U/f)>BF OFF
Relays
(U/f)AL
(U/f)AL
ST-K -
(U/f)AL
TR-K -
LEDs
(U/f)AL
(U/f)AL
ST-L -
(U/f)AL
TR-L -
tZ<<RES 0.10 s
Z<<def OFF
1.00 Zn
tZ<<def 1.00
Z<<TR-K -
LEDs Z<<
Z<<ST-L -
Z<<TR-L -
(U/f)AL Element