EasyManua.ls Logo

Thytronic Pro-N NVA100X-D - Phase Overcurrent 50;51 Side H and Side L - very Inverse Time Curve (ANSI;IEEE Type VI)

Thytronic Pro-N NVA100X-D
376 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
346
NVA100X-D - Manual - 02 - 2016
APPENDIX
Phase overcurrent 50/51 side H and side L - Very inverse time curve (ANSI/IEEE type VI)
F_51-ANSIVI-Char.ai
1.1
2 3 4 5 6 7 8 9 10 20
0.01
0.1
1
10
100
1000
10000
t [s]
10 s
60 s
5 s
1 s
0.5 s
0.2 s
0.1 s
0.02 s
t =
t
(H)
>
inv
·
[(I/I
(H)
>
inv
)
2
-1]
3.922
+ 0.092
t =
t
(L)
>
inv
·
[(I/I
(L)
>
inv
)
2
-1]
3.922
+ 0.092
Note: match of operating and setting time takes place when I/I
(H)
>
inv
or I/I
(L)
>
inv
= 2.306
I /I
(H)
>inv
I /I
(L)
>inv
t
(H)
>
inv
t
(L)
>
inv