EasyManua.ls Logo

Thytronic Pro-N NVA100X-D - Ground Directional Overcurrent 67 N(Comp) - Electromechanical Inverse Curves (EM)

Thytronic Pro-N NVA100X-D
376 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
366
NVA100X-D - Manual - 02 - 2016
APPENDIX
Ground directional overcurrent 67N(Comp) - Electromechanical inverse curves (EM)
F_67N-EM-Char.ai
1.1
2 345678910 20
0.01
0.1
1
10
100
1000
10000
t [s]
I
EDC
/I
EDH
>inv
I
EDC
/I
EDH
>>inv
I
EDC
/I
EDL
>inv
I
EDC
/I
EDL
>>inv
0.1 s
0.02 s
10 s
5 s
1 s
0.5 s
0.2 s
60 s
Note: match of operating and setting time takes place when I
EDC
/I
EDH
>
inv
= 4 or I
EDC
/I
EDH
>>
inv
= 4
t =
t
EDC
>
inv
t
EDC
>
inv
·
[-0.236 · (I
EDC
/I
EDH
>
inv
)
-1
+ 0.339]
0.28
t =
t
EDC
>
inv
·
[-0.236 · (I
EDC
/I
EDL
>
inv
)
-1
+ 0.339]
0.28
t =
t
EDC
>>
inv
·
[-0.236 · (I
EDC
/I
EDH
>>
inv
)
-1
+ 0.339]
0.28
t =
t
EDC
>>
inv
t
EDC
>>
inv
·
[-0.236 · (I
EDC
/I
EDL
>>
inv
)
-1
+ 0.339]
0.28

Table of Contents