Maintenance Procedures - Hydraulic Quantium 310 Maintenance Manual
Page 4-28 Document Ref 941113-001 Rev 2
4) Using a 10mm spanner, loosen and remove the nut and serrated
washer on the underside of the top plate to disconnect the
earth cable.
5) Carefully lift the hydraulic top plate out and place in a safe
position.
6) Use the wirecutters to remove the W&M seals from the meter
and pulser.
7) Using a 3mm allen key, loosen and remove the four hex cap
screws on the pulser casing. Disconnect the pulser and cable
from the pulser casing and move clear of the meter.
8) EPZ PUMPS ONLY
Using a 10mm spanner, loosen and remove the two screws
on the pump connection at the bottom of the meter to
disconnect the meter inlet pipe.
Disconnect the inlet pipe completely.
WARNING : BEWARE OF FUEL SPILLAGE.
9) PAS V3 PUMPS ONLY
Using a 13mm spanner, loosen and remove the two screws
and nuts on the pump connection at the bottom of the meter
to disconnect the meter inlet pipe.
Disconnect the inlet pipe completely.
WARNING : BEWARE OF FUEL SPILLAGE.
10) Using a 13mm spanner, loosen and remove the two screws
on the meter outlet pipe at the top of the meter.
11) Disconnect the meter outlet pipe and remove o-ring
completely.
WARNING : BEWARE OF FUEL SPILLAGE.
12) Carefully lift the meter out of the dispenser and place in a
safe position.
WARNING : BEWARE OF FUEL SPILLAGE.