Loading...
118 GX9 ASD Installation and Operation Manual
RX2 Input Point 1 Torque
Program Torque Setpoints
This parameter is used to set the gain and bias of the RX2 terminal when the
RX2 terminal is used as the control input while operating in the Torque
Control mode.
Note: The Expansion IO Card Option 1 option board (P/N ETB003Z)
is required to use this terminal.
The bias and gain of the RX terminal may be trimmed at F476 and F477,
respectively.
RX2 Torque Control Setup
Perform the following setup to allow the system to receive Torque Control
input at the RX2 terminal:
•Program Fundamental Standard Mode Selection Frequency Mode
RX2.
•Program Fundamental Standard Mode Selection Command Mode
Selection Terminal Board.
•Provide a Run command (F and/or R).
•Set RX2 Input Point 1 Torque (F226).
•Set RX2 Reference Point 1 (F222) — the input analog signal level that
corresponds to the speed setting at RX2 Input Point 1 Torque.
•Set RX2 Input Point 2 Torque (F227).
•Set RX2 Reference Point 2 (F224) — the input analog signal level that
corresponds to the speed setting at RX Input Point 2 Torque.
•Provide a Run command (F and/or R).
Torque Control is accomplished by establishing an associated V/f output
pattern for a given RX2 level.
Once set, as the RX2 voltage changes, the ASD output speed and/or torque will
vary in accordance with the above settings.
This parameter sets
RX2 Input Point 1 Torque and is the output torque value
that is associated with the setting of RX2 Reference Point 1 when operating in
the Torque Control mode.
This value is entered as -250% to +250% of the rated torque.
See the Expansion IO Card Option 1 instruction manual (D/N 58685) for
more information on the function of this terminal.
Direct Access Number — F226
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — -250.00
Maximum — +250.00
Units — %
Torque Settings
F226 F226