128 GX9 ASD Installation and Operation Manual
Jump Frequency 3
Program Special Jump Frequencies
Same as Jump Frequency 1 (F270) and is used when multiple frequencies are
to be jumped (see the plus-or-minus value setting at F275).
When multiple jump frequencies overlap, the system will recognize the lowest
and the highest frequencies as one jump range.
Direct Access Number — F274
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
Jump Frequency 3 Bandwidth
Program Special Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency 3
(F274).
Direct Access Number — F275
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — Hz
Jump Frequency Processing Selection
Program Special Jump Frequencies
This parameter determines if the output frequency of the ASD or the PID
feedback signal will be used as a reference for determining the Jump
Frequency range.
See F270 for further information on the Jump Frequency settings.
Settings:
0 — Process Amount
1 — Output Frequency
Direct Access Number — F276
Parameter Type — Selection List
Factory Default — Process Amount
Changeable During Run — Yes
Preset Speed 8
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 1000 and is
identified as Preset Speed 8. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see F018 for more information on
this parameter).
Direct Access Number — F287
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed 9
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 1001 and is
identified as Preset Speed 9. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see F018 for more information on
this parameter).
Direct Access Number — F288
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
F274 F288