128 GX9 ASD Installation and Operation Manual
Jump Frequency 3
Program Special Jump Frequencies
Same as Jump Frequency 1 (F270) and is used when multiple frequencies are
to be jumped (see the plus-or-minus value setting at F275).
When multiple jump frequencies overlap, the system will recognize the lowest
and the highest frequencies as one jump range.
Direct Access Number — F274
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
Jump Frequency 3 Bandwidth
Program Special Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency 3
(F274).
Direct Access Number — F275
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — Hz
Jump Frequency Processing Selection
Program Special Jump Frequencies
This parameter determines if the output frequency of the ASD or the PID
feedback signal will be used as a reference for determining the Jump
Frequency range.
See F270 for further information on the Jump Frequency settings.
Settings:
0 — Process Amount
1 — Output Frequency
Direct Access Number — F276
Parameter Type — Selection List
Factory Default Process Amount
Changeable During Run — Yes
Preset Speed 8
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 1000 and is
identified as Preset Speed 8. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see F018 for more information on
this parameter).
Direct Access Number — F287
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed 9
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 1001 and is
identified as Preset Speed 9. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see F018 for more information on
this parameter).
Direct Access Number — F288
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
F274 F288