GX9 ASD Installation and Operation Manual 149
Preset Speed 13 Direction
Program Frequency Preset Speed Modes
Determines the forward/reverse setting for the Preset Speed 13
(
F292).
Settings:
Forward
Reverse
Direct Access Number — F393
Parameter Type — Selection List
Factory Default Forward
Changeable During Run — No
Preset Speed 14 Direction
Program Frequency Preset Speed Modes
Determines the forward/reverse setting for the Preset Speed 14
(
F293).
Settings:
Forward
Reverse
Direct Access Number — F394
Parameter Type — Selection List
Factory Default Forward
Changeable During Run — No
Preset Speed 15 Direction
Program Frequency Preset Speed Modes
Determines the forward/reverse setting for the Preset Speed 15
(
F294).
Settings:
Forward
Reverse
Direct Access Number — F395
Parameter Type — Selection List
Factory Default Forward
Changeable During Run — No
Autotune and Reset Configuration
Program Motor Vector Motor Model
This parameter sets the Autotune command status.
Settings:
0 — Autotune Disabled
1 — Reset Motor Defaults
2 — Perform Autotune on Run Command
Direct Access Number — F400
Parameter Type — Selection List
Factory Default Autotune Disabled
Changeable During Run — No
Slip Frequency Gain
Program Motor Vector Motor Model
This parameter provides a degree of slip compensation for a given load. A
higher setting here decreases the slip allowed for a given load/ASD output ratio.
Direct Access Number — F401
Parameter Type — Numerical
Factory Default 0.60
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.55
Motor Constant 1 (primary resistance)
Program Motor Vector Motor Model
This parameter is the measurement of the stator resistance and is considered a
Motor Constant (unchanging). This value is used in conjunction with other
constants to tune the motor.
To use Vector Control, Automatic Torque Boost, or Automatic Energy-
saving, the Motor Constant setting (motor tuning) is required.
Direct Access Number — F402
Parameter Type — Numerical
Factory Default (ASD-Dependent)
Changeable During Run — No
Minimum — 0.0
Maximum — Open
Units — m
F393 F402