GX9 ASD Installation and Operation Manual 167
Acceleration/Deceleration Pattern 3
Program Special Accel/Decel (1 – 4) Settings
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the 3 Accel/Decel
parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
Direct Access Number — F512
Parameter Type — Selection List
Factory Default — Linear
Changeable During Run — Yes
Acceleration/Deceleration Switching Frequency 2
Program Special Accel/Decel Special
This parameter sets the frequency at which the acceleration control is switched
from the Accel 2 profile to the Accel 3 profile during a multiple-acceleration
profile configuration.
Direct Access Number — F513
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
Acceleration Time 4
Program Special Accel/Decel (1 – 4) Settings
This parameter specifies the time in seconds for the output of the ASD to go
from 0.0 Hz to the Maximum Frequency for the 4 Acceleration profile. The
Accel/Decel pattern may be set using F502. The minimum Accel/Decel time
may be set using F508.
Note: An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel, Stall, and Ridethrough settings may lengthen the
acceleration times.
Direct Access Number — F514
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — Acc/Dec Lower Limit
(F508)
Maximum — 6000.00
Units — Seconds
Deceleration Time 4
Program Special Accel/Decel (1 – 4) Settings
This parameter specifies the time in seconds for the output of the ASD to go
from the Maximum Frequency to 0.0 Hz for the 4 Deceleration profile. The
Accel/Decel pattern may be set using F502. The minimum Accel/Decel time
may be set using F508.
Note: A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel, Stall, and Ridethrough settings may lengthen the
deceleration times.
Direct Access Number — F515
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — Acc/Dec Lower Limit
(F508)
Maximum — 6000.00
Units — Seconds
F512 F515