168 GX9 ASD Installation and Operation Manual
Acceleration/Deceleration Pattern 4
Program Special Accel/Decel (1 – 4) Settings
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the 4 Accel/Decel
parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
Direct Access Number — F516
Parameter Type — Selection List
Factory Default Linear
Changeable During Run — Yes
Acceleration/Deceleration Switching Frequency 3
Program Special Accel/Decel Special
This parameter sets the frequency at which the acceleration control is switched
from the Accel 3 profile to the Accel 4 profile during a multiple-acceleration
profile configuration.
Direct Access Number — F517
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
F516 F517