204 GX9 ASD Installation and Operation Manual
Send Waiting Time (RS232/RS485)
Program Communications Communication Settings
This parameter sets the RS232/RS485 response delay time.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F825
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
ASD-to-ASD Communication (RS232/RS485)
Program Communications Communication Settings
In a master/follower configuration, this setting determines the output parameter
of the master ASD that will be used to control the applicable follower ASDs.
Note: Select No Follower if F806 is configured as a Master Output
controller. Otherwise, an EOI failure will result.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Settings:
0 — Normal (No Follower)
1 — Frequency Command
2 — Output Command Frequency
3 — Torque Command
4 — Output Torque Command
Direct Access Number — F826
Parameter Type — Selection List
Factory Default Normal (no follower)
Changeable During Run — Yes
Command Request Disposition on Error
Program Communications Scan Settings
In the event of a communication error during a transmission, the command that
was transmitted may be cleared or held.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Settings:
0 — Command Request Cleared
1 — Command Request Held
Direct Access Number — F830
Parameter Type — Selection List
Factory Default Command Request
Cleared
Changeable During Run — Yes
Input Reference 1
Program Communications Scan Settings
Not Used.
Direct Access Number — F831
Parameter Type — Numerical
Factory Default 0
Changeable During Run — Yes
Input Reference 2
Program Communications Scan Settings
Not Used.
Direct Access Number — F832
Parameter Type — Numerical
Factory Default 0
Changeable During Run — Yes
Input Reference 3
Program Communications Scan Settings
Not Used.
Direct Access Number — F833
Parameter Type — Numerical
Factory Default 0
Changeable During Run — Yes
F825 F833