210 GX9 ASD Installation and Operation Manual
Transducer Maximum Reading
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the maximum level of the transducer range for Virtual Linear
Pump operation.
Note: The unit of measure for this parameter is selected at the Virtual
Linear Pump Setup. The default setting is PSI.
Direct Access Number — F916
Parameter Type — Numerical
Factory Default 0
Changeable During Run — Yes
Minimum — -3276.7
Maximum — 3276.7
Virtual Linear Pump Minimum
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the minimum setpoint within the Virtual Linear Pump operating
domain.
Direct Access Number — F917
Parameter Type — Numerical
Factory Default 10.00
Changeable During Run — Yes
Minimum — 10.00
Maximum — F918 Setting
Virtual Linear Pump Maximum
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the maximum setpoint within the Virtual Linear Pump operating
domain.
Direct Access Number — F918
Parameter Type — Numerical
Factory Default 10.00
Changeable During Run — Yes
Minimum — F917 Setting
Maximum — 200.00
Virtual Linear Pump Low Frequency Limit
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the Virtual Linear Pump Low Frequency Limit.
Direct Access Number — F919
Parameter Type — Numerical
Factory Default 15.00
Changeable During Run — Yes
Minimum — 10.00
Maximum — 60.00
Units — Hz
Virtual Linear Pump Command Source
Program Virtual Linear Pump Settings
During Direct mode or the Process Hold mode operation, this parameter sets
the Virtual Linear Pump command source.
Settings:
0 — EOI
1 — *VI/II
2 — RR
3 — Communication Option
Note: Selecting VI/II here will result in an error message if Process
Hold is selected at F911.
Direct Access Number — F920
Parameter Type — Selection List
Factory Default EOI
Changeable During Run — No
F916 F920