GX9 ASD Installation and Operation Manual 209
Application Type
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the process variable measurement type.
Settings:
0 — Pressure
1 — Flow
2 — Level
Direct Access Number — F912
Parameter Type — Selection List
Factory Default — Pressure
Changeable During Run — No
Application Type Mode
Program Virtual Linear Pump Settings
While operating in the Virtual Linear Pump mode, this parameter sets the
system response to the received feedback from the VI terminal.
Select Direct Acting to produce an increase in the ASD output with a decrease
in the feedback signal.
Select Reverse Acting to produce a decrease in the ASD output with a decrease
in the feedback signal.
Settings:
0 — Direct Acting (Positive Gradient)
1 — Reverse Acting (Negative Gradient)
Direct Access Number — F913
Parameter Type — Selection List
Factory Default — Direct Acting
Changeable During Run — No
Transducer Output Range
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the transducer output signal type and range for Virtual Linear
Pump operation.
Note: This parameter is scaled at F201 – F204 for either selection and
requires no user intervention.
Settings:
0 — 0 – 20 mA
1 — 4 – 20 mA
2 — 0 – 10 V
3 — 0 – 5 V
Direct Access Number — F914
Parameter Type — Selection List
Factory Default — 4 – 20 mA
Changeable During Run — No
Transducer Minimum Reading
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this parameter
establishes the minimum level of the transducer range for Virtual Linear
Pump operation.
Note: The unit of measure for this parameter is selected at the Virtual
Linear Pump Setup. The default setting is PSI.
Direct Access Number — F915
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -3276.7
Maximum — 3276.7
F912 F915