GX9 ASD Installation and Operation Manual 213
Virtual Linear Pump Low Start/Stop Point
Virtual Linear Pump Start and Stop Points
During a properly configured Virtual Linear Pump operation while in the On
Forward or On Reverse modes (F927), this parameter establishes the lower
level of the Auto Start-Stop threshold.
See F927 for further information on this parameter.
The unit of measure for this parameter may be one of the following types — the
type is selected while running the Setup Wizard.
•PSI
•GPM
Inches of Water Column
Feet of Water Column
•CFM
•°C
•°F
•*Custom
Note: Custom selection allows for three character spaces to be
populated from the list of 26 alphabet and 13 special characters.
Direct Access Number — F929
Parameter Type — Numerical
Factory Default Application-Specific
Changeable During Run — Yes
Minimum — -3276.7
Maximum — 3276.7
Units — Selectable at Virtual Linear
Pump Setup Wizard
Virtual Linear Pump High Start/Stop Point
Virtual Linear Pump Start and Stop Points
During a properly configured Virtual Linear Pump operation while in the On
Forward or On Reverse modes (F927), this parameter establishes the upper
level of the Auto Start-Stop threshold.
See F927 for further information on this parameter.
The unit of measure for this parameter may be one of the following types — the
type is selected while running the Setup Wizard.
•PSI
•GPM
Inches of Water Column
Feet of Water Column
•CFM
•°C
•°F
•*Custom
Note: Custom selection allows for three character spaces to be
populated from the list of 26 alphabet and 13 special characters.
Direct Access Number — F930
Parameter Type — Numerical
Factory Default 300.0
Changeable During Run — Yes
Minimum — -3276.7
Maximum — 3276.7
Units — Selectable at Virtual Linear
Pump Setup Wizard
F929 F930