214 GX9 ASD Installation and Operation Manual
Virtual Linear Pump External Device Delay Timer
Virtual Linear Pump Run External Devices
During a properly configured Virtual Linear Pump operation, this parameter
establishes the time that the Virtual Linear Pump operating level must remain
within the Maximum Threshold Zone or the Minimum Threshold Zone to
activate/deactivate the Sleep Timer (F925) or an auxiliary pump.
See Figures 29 and 30 for more information on the Maximum Threshold Zone
and the Minimum Threshold Zone.
Increasing Load
If the Virtual Linear Pump operating level of the Lead Pump is within the
Maximum Threshold Zone, and the External Device Delay Timer times out,
OUT1 will change states and activate an auxiliary pump (Lag1).
Should the Virtual Linear Pump operating level return to the Maximum
Threshold Zone for a duration in excess of the External Device Delay Timer,
OUT2 will change states and activate the second auxiliary pump (Lag2).
Decreasing Load
If operating in the Minimum Threshold Zone, and the External Device Delay
Timer times out while OUT2 is activated, OUT2 will change states and
deactivate the second auxiliary pump (Lag2).
Should the system return to the Minimum Threshold Zone for a duration in
excess of the External Device Delay Timer, OUT1 will change states and
deactivate the auxiliary pump (Lag1).
Note: Set the Sleep Timer Delay (F926) to two (2) times the Virtual
Linear Pump External Device Delay Timer (if using the Sleep
Timer function) as not to place the primary ASD in the sleep
mode with Lag1 and/or Lag2 running.
Note: Set OUT1 and OUT2 to External Device 1 and 2, respectively,
as required.
Direct Access Number — F931
Parameter Type — Numerical
Factory Default 5
Changeable During Run — Yes
Minimum — 0.0
Maximum — 6553.5
Units — Seconds
x
ternal Device
x
ternal
e
vice 2
Auxiliary Pump Activation Sequence
PUMP ID IF @ AND THEN OR
Lead Pump Max Zone Counter Time = 0
Activate
OUT1
Lag1 Pump Max Zone Counter Time = 0
Activate
OUT2
Lag2 Pump Max Zone Counter Time = 0
Run
Continuous
Lag2 Pump Min Zone Counter Time = 0
Deactivate
OUT2
Lag1 Pump Min Zone Counter Time = 0
Deactivate
OUT1
Lead Pump Min Zone Counter Time = 0
Sleep if
enabled
Note: The number of pumps used
may be increased by using
the optional expansion
board (Primary pump plus
auxiliary pumps).
F931 F931