GX9 ASD Installation and Operation Manual 81
Motor Overload Protection Configuration
Program Protection Overload
This parameter is used to protect the motor from an over-current condition. The
type of motor being used and the Overload Stall setting is selected here to
better match the application.
This parameter setting may extend the Over-Voltage Limit Operation (F305)
time settings.
This parameter may be affected by the setting of the Power Running Stall
Continuous Trip Detection Time (F452).
Parameter F452 (Power Running Stall Continuous Trip Detection Time) setting
may affect the performance of this parameter setting.
Settings:
0 — Motor OL Trip and No Soft Stall
1 — Motor OL Trip with Soft Stall
2 — No Motor OL Trip and No Soft Stall
3 — Soft Stall Only
4 — V/f Motor OL Trip and No Soft Stall
5 — V/f Motor OL Trip with Soft Stall
6 — V/f Motor with NO OL Trip and No Soft Stall
7 — V/f Motor Soft Stall Only
Direct Access Number — F017
Parameter Type — Selection List
Factory Default — Motor OL Trip and
No Soft Stall
Changeable During Run — No
F017 F017