86 GX9 ASD Installation and Operation Manual
Forward/Reverse Run Priority When Both Are Activated
Program Terminal Input Special Functions
The Forward/Reverse Priority Selection determines the operation of the ASD
if the F and R control terminals are activated simultaneously.
Settings:
0 — Reverse
1 — Suspend
The waveforms shown depict the motor response for all combinations of the F
and R terminal settings if the Reverse option is chosen.
The Suspend setting will decelerate the motor to a stop regardless of the
rotation direction when both the F and R control terminals are activated.
Direct Access Number — F105
Parameter Type — Selection List
Factory Default Reverse
Changeable During Run — No
Simultaneous F and R activation.
Input Terminal Priority Selection
Program Terminal Input Special Functions
This parameter is used to allow the Jog and DC Injection Braking input
signals to control the ASD when received via the Terminal Board even though
the system is in the Local mode.
With this parameter enabled, a Jog command or a DC Injection Braking
command received from the Terminal Board will receive priority over
commands from the EOI.
See F260 for more information on using the Jog function.
See F250 F252 for more information on DC Injection Braking.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F106
Parameter Type — Selection List
Factory Default Disabled
Changeable During Run — No
F105 F106