GX9 ASD Installation and Operation Manual 87
16-Bit Binary/BCD Input Selection
Program Terminal Input Special Functions
The extended terminal function is used with the Expansion IO Card Option
(P/N ETB004Z).
This parameter defines the format of the binary or BCD data when using the
option card.
Note: The Expansion IO Card Option 2 option board is required to
use this terminal.
See the Expansion IO Card Option 1 instruction manual (D/N 58685) for
more information on the function of this terminal.
Settings:
0 — None
1 — 12-Bit Binary
2 — 16-Bit Binary
3 — 3-Digit BCD
4 — 4-Digit BCD
5 — Inverted 12-Bit Binary
6 — Inverted 16-Bit Binary
7 — Inverted 3-Digit BCD
8 — Inverted 4-Digit BCD
Selections using 16-bit binary or 4-digit BCD will require the configuration of
terminals S1-S4 on the Terminal Board as binary bits 0 – 3 (F115F118). The
Frequency Mode 1 (F004) parameter must be set to Binary/BCD.
For proper scaling of the binary or BCD input, parameters F228 F231 must be
configured.
Direct Access Number — F107
Parameter Type — Selection List
Factory Default None
Changeable During Run — No
F107 F107