85 
 
■ BUM7B power supply wiring 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 3.3 BUM7B power supply wiring 
 
 
Frame ground terminal (FG): Connected to the base unit chassis. 
For details, refer to “3.4 Grounding.” 
 
Important 
• The M3.5 screw is used for securing the terminal. Use an appropriate crimp-type 
terminal with a width of 7 mm or less for the M3.5 screw (tightening torque: approx. 
1.0N・m). 
 
Remark 
• Take into account the leak current of the BUM7B power supply and noise filter in 
designing the system. 
 
 
 
RUN contact output 
240Vac (+10%) / 24Vdc (+20%)
Max. 2A
 
Input power 
100/240Vac 
Max. 1.5A. 
50/60Hz 
Connect a power supply 
suitable for rating 
Failure to do so may cause 
ex
losion or fire. 
Ferrite core
2-turn 
Noise 
filter 
Shielded 
transformer
Use a twisted-pair cable of 1.25mm
2