Chapter 2 System Migration Procedures
6E8C5563
22
2
2.1.3 Power Supply Module
T2 series power supply modules (PS261/PS31) are converted to PS693/PS632 for nv
controller type1 light.
Table 2.5 T2 series power supply module conversion
After conversion
Before conversion
nv type1 light
PS693 PS632 PS652
PROSEC
T series
T2
PS261 ○ × ×
PS31
× ○ ×
○: Convertible, ×: Not convertible
Table 2.6 Comparison of power supply module specifications
T2 series nv controller type1 light
PS261 PS31 PS693 PS632 PS652
Rated voltage AC100-240V DC24V AC100-120V/
AC200-240V
DC24V DC100/110V
Allowable voltage
range
AC85-264V DC20.4-28.8V AC85-264V DC20.4-28.8V DC85-132V
Rated frequency 50/60Hz
(47-63Hz)
DC 50/60Hz
(47-53/57-63Hz)
DC DC
Allowable
instantaneous
outage time
10ms or less 10ms or less
Rated current 53VA or less 22W or less 120VA(50W) or
less
50W or less 50W or less
Inrush current AC100V-15A/
AC200V-35A
or less
30A/10ms or less
(DC24V)
AC240V-12A
peak or less
6.5A/10ms or less
(during rated input )
25A or less
(during rated input )
Output rating 5V-2.5A
24V-0.5A
Total 15W or less
5V-2.5A
24V-0.5A
Total 15W or less
5V-7A
3.3V-1.0A
24V-0.8A
Total 35W or less
5V-7A
3.3V-1.0A
Total 35W or less
5V-7A
3.3V-1.0A
Total 35W or less
Insulation
resistance
DC500V-10MΩ or more
(Between input and output, and
input and FG)
DC500V-10MΩ or more (Between input and output,
and input and FG)
Dielectric
strength voltage
AC1500V/ 1 minute(Between input
and output, and input and FG)
AC2500V/ 1 minute(Between input and output, and
input and FG)
Grounding Class 3 grounding
*1
Class D grounding (dedicated)
Status display POWER(Red) POWER(Green)
RUN contact Dry A contact
AC240V/DC24V-2Amax
Dry A contact
AC240V/DC24V-0.2Amax.
External lines 10 terminal・M3.5 screw (Detachable) 9 terminal・M3.5 screw(Fixed)
*1: Currently used class D grounding
×:
◆Remarks:
Not all specifications are listed in the above comparison table.
Confirm the specification in the relevant instruction manual.