The connection of the PS361 power terminal is shown below for reference. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure A.7 Connection of PS361 power terminal (for reference) 
 
 
[Grounding] 
The ideal ground of electronic devices is the dedicated ground separately provided from 
the power system, and a single-point ground for two or more devices. The nv series 
unified controller is designed to be noise tolerable in consideration of practical 
applications and the controller itself has a sufficient noise resistivity. Even so, proper 
grounding is important for the security and reliability of the controller. 
Keep the following notes for grounding: 
・Prevent the enclosure of electronic device from being a path for ground current 
(especially high-frequency current). 
・Make the ground potential of two or more electronic devices equivalent when 
connecting them (a single-point ground is the best practice). 
・Do not connect the electronic device to the power system ground (high-frequency 
isolation is required). 
・Do not connect the electronic device to an unstable ground (e.g. unstable impedance 
area such as screwed and painted part, or area subject to vibration). 
 
Important 
Be sure to ground the controller. Operation without grounding may cause electric shock or 
malfunction. 
 
 
 
Operating signal output   
(RUN) 
100Vac line: Shorted 
200Vac line: Opened 
100 - 200Vac 
or 
200 - 240Vac
 
Ground