T series Migration User’s Manual - Hardware -
53
2
Table 2.27 Comparison of power module specifications
T3 series nv controller type1 light
PS361
PS332/
PS332A
BUM7B PS693 PS632 PS652
Rated voltage AC100/200V DC24V AC100-120V/
AC200-240V
AC100-120V/
AC200-240V
DC24V DC100/110V
Allowable voltage
range
AC85-132V/
AC170-264V
(Terminal
switching)
DC20.4-28.8V AC85-264V AC85-264V DC20.4-28.
8V
DC85-132V
Rated frequency 50/60Hz
(47-63Hz)
DC 50/60Hz
(47-53/57-63Hz)
50/60Hz
(47-53/57-63
Hz)
DC DC
Allowable
instantaneous
outage time
10ms or less 10ms or less 10ms or less
Consumption
current (max.)
80VA or less 50W or less -
120VA(50W)
or less
50W or less 50W or less
Rated current - - AC100V-
1.5Amax
*1
AC200V-
0.75A max
*1
- - -
Inrush current AC100V-10A/
AC200V-20A
or less
6.5A or less
(DC24V)
AC100V-14A/
AC200V-28A
or less
AC240V-12A
peak or less
6.5A/10ms
or less
(during
rating input)
25A or less
(during rating
input)
Output rating 5V-7A 5V-7A 5V-10A
5V-7A
3.3V-1.0A
24V-0.8A
Total 35W or
less
5V-7A
3.3V-1.0A
Total 35W or
less
5V-7A
3.3V-1.0A
Total 35W or
less
Insulation
resistance
DC500V-10MΩ or more
(Between input and output,
and input and FG)
DC500V-10MΩor
more(Between
input and output,
and input and FG)
DC500V-10MΩ or more(Between input
and output, and input and FG)
Dielectric
strength voltage
AC1500V/1 minute
(Between input and output,
and input and FG)
AC2000V/ 1
minute(Between
input and output,
and input and FG)
AC2500V/ 1 minute (Between input and
output, and input and FG)
Grounding Class D grounding
(dedicated)
Class D grounding
(dedicated)
Class D grounding(dedicated)
Status display POWER(Green) POWER(Green) POWER(Green)
RUN contact Dry A contact
AC240V/DC24V-2Amax
Dry A contact
AC240V/DC24V-
2Amax
Dry A contact
AC240V/DC24V-0.2Amax.
External lines
terminal
8 terminal・M3.5 screw
(Detachable)
8 terminal ・M3.5
screw(Detachable)
9 terminal・M3.5 screw (Fixed)
*1: The rated current is typ.0.75A (100-120Vac) or typ.0.375A (200-240Vac) at an output rating
of 5Vdc-10A.
◆Remark:
Not all specifications are listed in the above comparison table.
Confirm the specification in the relevant instruction manual.