• BUM7B is used as T3/T3H expansion base unit:
Table 2.32 Conversion of T3/T3H expansion base unit to PUM12 remote base unit
Before conversion After conversion
T3/T3H(PU324/PU325/PU325H/PU326H) type1 light(PUM12)
BU
Slots
BU
Slots
0 1 2 3 4 5 6 7 8 9 10 S0 S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11
BU356 ▽ ▽ ▽ ▽ ▽ ▽ - - - - - BUM7B ★ ○ ○ ○ ○ ○ ○ × × × × ×
BU35B ▽ ▽ ▽ ▽ ▽ ▽ ▽ ▽ ▽ ▽ ▽ BUM7B ★ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
★: GA922
▽: G3 I/O module
○: G2 I/O module
×: Not mountable (set space module (SP600))
-: Not provided
● Important
• DI/DO, AD/DA and TM611 modules are supported in GA922. Consequently,
transmission modules (TL-S20, TL-F10, FL-net, etc.), registered in the T3 expansion
unit, are not converted.
T3/T3H
type1 light(PUM12)
PS
I/O
(0)
I/O
(1)
I/O
(2)
I/O
(4)
I/O
(3)
I/O
(5)
IF
BU356
(0)~(5):I/O Slot No.
BUM7B
G
(0)
I/O
(1)
I/O
(2)
I/O
(3)
I/O
(5)
I/O
(4)
I/O
(6)
SP
(7)
SP
(8)
(0)~(11):Slot No. S0~S11
SP
(9)
SP
(10)
SP
(11)
IF: Expansion interface module
PS: Power module
PU: PU324/PU325/PU325H/PU326H
I/O: G3 I/O module(Up to 6)
PU: PUM12
GA: GA922
I/O: G2 I/O module
(GA922: Up to 6)
SP: Space slot
PS
I/O
(0)
I/O
(1)
I/O
(2)
I/O
(4)
I/O
(3)
I/O
(5)
I/O
(6)
I/O
(7)
I/O
(8)
I/O
(9)
IF
I/O
(10)
BU35B
(0)~(10):I/O Slot No.
BUM7B
GA
(0)
I/O
(1)
I/O
(2)
I/O
(3)
I/O
(5)
I/O
(4)
I/O
(6)
I/O
(7)
I/O
(8)
(0)~(11):Slot No. S0~S11
I/O
(9)
I/O
(10)
I/O
(11)
IF: Expansion interface module
PS: Power module
PU: PU324/PU325/PU325H/PU326H
I/O: G3 I/O module(Up to 11)
PU: PUM12
GA: GA922
I/O: G2 I/O module
(GA922: Up to 11)