EasyManua.ls Logo

Tyco iSTAR Ultra - Maximum Power Ratings

Tyco iSTAR Ultra
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Power Requirements
iSTAR Ultra Installation and Configuration Guide 4–3
Dry Relay: 0 to 30 Vdc , 5A max. NO, 3A max. NC
Maximum Power
The ISTAR Ultra system power ratings are listed in Table 4-1 through Table 4-3.
Table 4-1: iSTAR Ultra GCM Rack System Ratings
Voltage
(Vdc)
Current
(A)
Local External
Circuit Breaker
Rating (A)
System Description
System Power Ratings:
12 4.49 - (1) GCM with (2) RS-485 Loads
Table 4-2: iSTAR Ultra ACM Rack Ratings
Voltage
(Vdc)
Current
(A)
Local External
Circuit Breaker
Rating (A)
System Description
System Power Ratings:
12 5 - (1) ACM with (3) Wiegand/RS485/Aux load
12 8 10 (1) ACM with (5) Wiegand/RS485/Aux load
12 9.5 12 (1) ACM with (6) Wiegand/RS485/Aux load
12 11 15 (1) ACM with (7) Wiegand/RS485/Aux load
12 12.5 29 (1) ACM with (8) Wiegand/RS485/Aux load
Lock 1 and 2 Power Ratings:
0 - 30 4.5 - (6) Locks
0 - 30 6 7.5 (8) Locks
0 - 30 7.5 10 (10) Locks
0 - 30 9 12 (12) Locks
0 - 30 12 15 (16) Locks
Table 4-3: iSTAR Ultra Wall Mount Ratings
Voltage
(Vdc)
Current
(A)
Local External
Circuit Breaker
Rating (A)
System Description
System Power Ratings (when sourcing both GCM and ACMs):
12 3.99 - (1) GCM with (1) RS-485 Loads & (2) ACM with no loads
12 4.99 - (1) GCM with (2) RS-485 Loads & (1) ACM with no loads
12 7.99 10 (1) GCM with (2) RS-485 Loads & (1) ACM with
(2) Wiegand/RS485/Aux load

Table of Contents

Related product manuals