Displaying Status Messages
10–4 iSTAR Ultra Installation and Configuration Guide
Displaying Status Messages
Under normal conditions, set the LCD to display status messages, including: 
 iSTAR boot information 
 Date and time 
 Firmware version 
 Controller status information. 
Messages typically display for approximately four seconds, separated by an interval of about 
one second. In some instances, however, a message can display until it is cancelled or 
terminated. 
Setting LCD Status Message Display
You can display LCD general status messages for a controller by setting the SW3 rotary switch 
to positions 0 (zero) or F. Setting the SW3 switch to 0 or F also controls the ICU Block feature, 
preventing or allowing users from modifying the ICU configuration, as shown in Table 10-2.
 When ICU Block is On (set SW3 to F) – the LCD displays general status messages; 
however, fields in the ICU dialog box are unavailable and cannot be edited. 
 With ICU Block Off (set SW3 to 0) – the LCD displays general status messages, and users 
can read, write, and update the ICU configuration. 
Table 10-2:  LCD Status Display Messages 
Rotary 
Switch 
SW3
 Display General 
Messages (Read only) 
ICU Block On
Display General Messages 
(Read/Write/Update) 
ICU Block Off 
Set SW3 to:  F  0