Power Requirements
4–4 iSTAR Ultra Installation and Configuration Guide
Additional Power Requirements
An external over-current protection device (i.e. circuit breaker) must be installed in a
secure location readily accessible to a service person.
12 9.49 12 (1) GCM with (2) RS-485 Loads & (1) ACM with
(3) Wiegand/RS485/Aux load
12 10.49 15 (1) GCM with (2) RS-485 Loads & (1) ACM with
(4) Wiegand/RS485/Aux load
12 15.49 20 (1) GCM with (2) RS-485 Loads & (1) ACM with
(7) Wiegand/RS485/Aux load
12 18.99 25 (1) GCM with (2) RS-485 Loads & (2) ACM with
(9) Wiegand/RS485/Aux load
12 23.49 30 (1) GCM with (2) RS-485 Loads & (2) ACM with
(12) Wiegand/RS485/Aux load
12 27.99 35 (1) GCM with (2) RS-485 Loads & (2) ACM with
(15) Wiegand/RS485/Aux load
12 29.49 40 (1) GCM with (2) RS-485 Loads & (2) ACM with
(16) Wiegand/RS485/Aux load
Lock 1 and 2 Power Ratings:
0 - 30 4.5 - (6) Locks
0 - 30 6 7.5 (8) Locks
0 - 30 7.5 10 (10) Locks
ac0 - 30 9 12 (12) Locks
0 - 30 12 15 (16) Locks
0 - 30 15.75 20 (21) Locks
0 - 30 19.5 25 (26) Locks
0 - 30 24 30 (32) Locks
Table 4-3: iSTAR Ultra Wall Mount Ratings, continued
Voltage
(Vdc)
Current
(A)
Local External
Circuit Breaker
Rating (A)
System Description