Inputs
iSTAR Ultra Installation and Configuration Guide 6–19
NO/NC Dual EOL 1K
Figure 6-15 on page 6-19 shows the traditional Software House method of supervision where
1K is considered Secure and 500 orare considered Alert. Notice that the wiring is
different for NO and NC.
Figure 6-15: NO / NC Dual EOL 1K
1K Double NC (Casi-Rusco) Serial and Parallel Resistors
Normal = 1K
Alert = 2K
1K Double NO (Casi-Rusco) Parallel and Serial Resistors
Normal = 2K
Alert = 1K
5K Double NC (Simplex) Serial and Parallel Resistors
Normal = 5K
Alert = 10K
5K Double NO (Simplex) Parallel and Serial Resistors
Normal = 10K
Alert = 5K
10K Double NC (Andover)
Normal = 5K
Alert = 10K
10K Double NO (Andover)
Normal = 10K
Alert = 5K
4.02K/8.04K Triple NC
(Atlantek)
Normal = 4.02K, Tamper = 10.06K
Alert = 8.04K, Tamper + Alarm = 14.08K
Table 6-8: Supervision Modes, continued
Mode Comment
For UL Listed products,
burglar alarms must be supervised.