3.13.6.5 DETECTOR POWER UP
Press 4 from the Switches menu. The following screen will
be displayed:
This allows the monitoring of detector removal to be
disabled.
3.14 CONFIGURATION
Press 8 from the Main menu. The following screen will be
displayed:
Menu option 9 will only be displayed if an action has been
carried out and saved. The relevant action will only be
carried out after the panel has been restarted.
After an action has been carried out, not all menu options
from the configuration menu are displayed.
RESTRICTIONS ON THE USE OF THE
FOLLOWING OPTIONS
When using Configuration menu options 2 to 4, ALWAYS
commit configuration changes by using option 9 ‘Restart’
before leaving the panel.
Avoid ‘inactivity’ timeouts.
NEVER use the ‘Back’ option from the configuration
menu if option 9 ‘Restart’ is showing.
If you do not want to commit changes, by using 9 ‘Restart’,
option, turn the keyswitch to ‘OFF’ position to avoid a
timeout situation, do NOT USE the ‘Back’ option.
MX Panel
Wed, 01-Mar-08
14:15
Company Name
General
Back
Detector Power Up
Status: ENABLED
2 - Disable
MX Panel
Wed, 01-Mar-00
14:15
Company Name
General
Back
Configuration
1 - Change Text
2 - Insert Point
3 - Delete Point
4 - Modify Point
7 - Autoconfig.
9 - Restart
Configuration changes across a network are possible, but
changes to more than one panel at a time MUST NOT be
attempted within one session. When a panels
configuration has been changed, it must be restarted using
menu option 9 ‘Restart’.
Failure to comply with these restrictions may lead to
unpredictable effects or system instability
3.14.1 CHANGE TEXT
Press 1 from the Configuration menu. The following
screen will be displayed:
3.14.1.1 POINT TEXT MODIFY
Press 1 from the Change Text menu. The following screen
will be displayed:
Select the required loop and point then press Enter. The
following type of screen will be displayed:
MX Panel
Wed, 01-Mar-08
14:15
Company Name
General
Back
Change Text
1 - Point Text
2 - Zone Text
3 - Sector Text
4 - Panel Text
5 - Info Text
MX Panel
Wed, 01-Mar-08
14:15
Company Name
General
Back
Point Text Modify
Loop : A
Point : 001
>>
-
+ Enter
MX Panel
Wed, 01-Mar-08
14:15
Company Name
General
Back
Point Text Modify
Zone 255 -007 A
Old text
Callp. alarm room
New text
>>
-
+ Enter