YK11-0016-DI-002-08
37
MODEL MOTOR Speficication
the
connection
inside the
terminal box
Rated
Current
(Voltage-
Frequency)
Breaker Thermal relay
Recommended
Magnetic motor
starters
Recommende
d
Wire Gauge
Applicable
Wire Gauge
Recommende
d
Wire Gauge
Applicable
Wire Gauge
Recommende
d
Wire Gauge
Applicable
Wire Gauge
Terminal
Crimp-type
terminal lug
JST
Corporation
kw A A
Fuji Electric FA
Components &
Systems Co.,Ltd.
Size・Form N・m
25.7A 25.7A
(200V-50Hz) (200V-50Hz)
23.9A 23.9A
(220V-50Hz) (220V-50Hz)
23.8A 23.8A
(240V-50Hz) (240V-50Hz)
25.7A 25.7A
(200V-60Hz) (200V-60Hz)
24.4A 24.4A
(208V-60Hz) (208V-60Hz)
23.0A 23.0A
(220V-60Hz) (220V-60Hz)
21.7A 21.7A
(240V-60Hz) (240V-60Hz)
13.8A 13.8A
(380V-50Hz) (380V-50Hz)
13.8A 13.8A
(415V-50Hz) (415V-50Hz)
13.5A 13.5A
(380V-60Hz) (380V-60Hz)
11.9A 11.9A
(460V-60Hz) (460V-60Hz)
For Japan For America For Europe and China
PMB2400D 7.5
Motor :
Multi rated
delta
40
8mm
2
8mm
2
SW-N1
or SW-N1/2L
200V
18A-26A
SW-4-1
or SW-4-1/2L
400V
12A-18A
SW-4-1 400V
or SW-4-1/2L
9A-13A
star
2.0-2.5 R8-5
M6
Cross
recessed
head screw
4.0-5.0 R8-6
AWG8 AWG8
8mm
2
8mm
2
U1
V1
W1
M5
Hexagon nut
Width across
flat: 8mm
CAUTION
It is recommended that you install a leakage breaker dedicated.
Sure to attach overload protection device. If you do not attach the overload protection device, burnout
of the motor, causing a fire.
The wire size, please decide by considering the voltage drop of the wire.
Typically, voltage drop, please set to be within 2% of the motor rated voltage.
Voltage drop formula
Motor rated voltage (V) × 0.02 ≧
Wiring distance √ 3 × wire resistance (Ω / km) × wire length (m) × motor rated current(A) × 10 -3