Measured and recorded values of synchrocheck stage
SyC1 (25):
Measured frequency
difference
Measured voltage
amplitude and phase
angle difference
Measured frequency
(reference side)
Measured frequency
(comparison side)
Measured voltage
(reference side)
Measured voltage
(comparison side)
Recorded frequency
(reference side)
Recorded frequency
(comparison side)
Recorded voltage
(reference side)
Recorded voltage
(comparison side)
Recorded phase angle
difference, when close
command is given from
the function
Recorded phase angle
difference, when the
circuit-breaker actually
closes.
The elapsed time
compared to the set
request timeout setting,
100% = timeout
1) Please note that the labels (parameter names) change according to the
voltage selection.
The following signals of the both stages are available in the
output matrix and the logic: ―Request‖, ―OK‖ and ―Fail‖. The
―request‖-signal is active, when a request has received but the
breaker is not yet closed. The ―OK‖-signal is active, when the
synchronising conditions are met, or the voltage check criterion
is met. The ―fail‖-signal is activated, if the function fails to close