4.11 Primary, secondary and per unit
scaling
VAMP 24h support phone +358 (0)20 753 3264
4.11. Primary, secondary and per unit
scaling
Many measurement values are shown as primary values
although the device is connected to secondary signals. Some
measurement values are shown as relative values - per unit or
per cent. Almost all pick-up setting values are using relative
scaling. The scaling is done using the given CT, VT ratios in the
―Scaling‖ of the relay.
Following scaling equations seen in the sub chapters are useful
when doing secondary testing.
4.11.1. Current scaling
NOTE! The rated value of the device's current input, 5 A, 1A or 0.2 A, does not
have any effect in the scaling equations, but it defines the measurement
range and the maximum allowed continuous current. See chapter 9.1.1
for details.
Primary and secondary scaling
For residual currents to input I
01
use the corresponding CT
PRI
and CT
SEC
values. For earth fault stages using I
0Calc
signals use
the phase current CT values for CT
PRI
and CT
SEC
.
Example 1: Secondary to primary.
CT = 500/5
Current to the device's input is 4 A.
Primary current is I
PRI
= 4x500/5 = 400 A
Example 2: Primary to secondary.
CT = 500/5
The device displays I
PRI
= 400 A
Injected current is I
SEC
= 400x5/500 = 4 A